CANopen Digital 32 Inputs

CANopen is an upper-layer communication protocol based on Controller Area Network, being one of the popular modern industry Fieldbus, drafted and developed by non-profit organization CiA (CAN in Automaion). The CiA drafts standard 301 definition basic CANopen equipment and sub-agreement. The sub-agreements of individual devices are further expansion based on CiA 301, such as CiA401 for I / O modules and CiA402 for motion control. CANopen adopts two-wire serial communication, and allows up to 127 devices in a CANopen network. The maximum transfer rate is 1Mbps / 40 meters, and the maximum transmission distance is 10,000 m / 5kbps. iModule series CANopen remote I/O is, via acquiring signals and communicating with the master station, to complete a reliable control of fieldbus devices.
| Part Number | 131-1BL00-CAN |
| Type | Digital input module |
| Degital Input Number of Input | 32 |
| Input Filter | 0.5ms |
| Nominal Output Voltage | 24VDC (-15%/+20%) |
| "1" Signal Voltage | 15~30VDC, 7mA |
| "0" Signal Voltage | 0~5VDC |
| Port protect | Impact over voltage protection |
| Voltage supply | 24 V DC(-15%/+20%) |
| Electrical isolation (Bus/Field potential) | AC 500V |
| Protocol | CANopen |
| Connector | D-Sub9 |
| Transmission rate | 10k~1Mbps((config by 3-bit dial switch) |
| Address config | 00~99(config by 2-bit dial switch) |
| Communication Profile | CiA DS-301 |
| Device Profile | CiA DS-401 |
| Device monitor | Heartbeat, Node Guarding |
| Installation | DIN Rail(TS35) |
| LED Indicate | PWR Green ERR Red |